Product Categories
Contact Us

Teaton Electric Co., Ltd.

Mobile: 008618355368712

Whats App: 0086 183 553 68712

Add: B Block, New Metropolis, Jinghu Century Town, Jinghu District, Wuhu City, Anhui Province, China

Zip Code: 241000

MN Undervoltage Release

MN Undervoltage Release opens the circuit breakers when its supply voltage drops to a value below 35% of rated voltage Un.
●Undervoltage tripping: combined with an emergency-off button, provides fail-safe tripping;
●If the supply voltage is between 0.35 and 0.7 Un, opening is possible, but not guaranteed. Above 0.7 Un, opening does not take place;
●The MN release is continuously supplied if supply is interrupted: either voluntarily through loss of power or faulty wiring;
●The MN release provokes opening circuit breaker;
MN/UVR was designed and developed by Merlin Gerin in early 2000, now it is newly marked as Schneider without any change.
Write to us for more details, and we will offer such items with excellent quality and competitive prices, thanks.

Products Specifications:

Features of MN Unvervoltage Release

■Energize control circuit, then turn circuit breaker On;

■De-energize control circuit;

■Circuit breaker shall trip;

■Coil resistance voltage can not be measured at accessory leads;

If accessory does not operate correctly, check wiring connection.

MN Undervoltage Release Technical Data

Power supply

VAC

50/60Hz: 24-48-100/130-200/240

50Hz: 380/415, 60Hz: 208/277

VDC

12-24-30-48-60-125-250

Operating threshold

Opening

0.35 to 0.7 Un

Closing

0.85 Un

Operating range

0.85 to 1.1 Un

Consumption, VA or W

Pick-up: 10, Hold: 5

Response time, ms

50

Side views of MN Undervoltage Release

views of mn.jpg

Hot Tags: MN Undervoltage Release, China, Manufacturers, Suppliers, Factory