Product Categories
Contact Us

Teaton Electric Co., Ltd.

Mobile: 008618355368712

Whats App: 0086 183 553 68712

Add: B Block, New Metropolis, Jinghu Century Town, Jinghu District, Wuhu City, Anhui Province, China

Zip Code: 241000

GV2ME Motor Circuit Breaker

GV2ME Motor Circuit Breaker is 3-pole thermal-magnetic circuit breaker specially designed for the control and protection of motors, conforming to standard IEC 60947-2 and IEC 60947-1 with the following features.
●Available in open or enclosed version;
●Fixed on the front panel or DIN rail mounted;
●Padlockable versions;
All machines requiring:
●Direct On-Line starting or stopping of motors;
●Load breaking of the machine control circuit;
●Enclosed DOL starters are used to control starting or stopping of the machine;

Products Specifications:

GV2ME Motor Circuit Breaker selection table

Reference

Setting range of thermal trips

Standard power ratings of 3-phase motors, 50/60Hz in category AC-3

400/415V

500V

690V

P,kW

Icu,kA

P,kW

Icu,kA

P,kW

Icu,kA

GV2ME08

2.50…4.00A

1.5

-

2.2

-

3

3

GV2ME10

4.00…6.30A

2.2

-

3

50

4

3

GV2ME14

6.00…10.0A

4

-

5.5

10

7.5

3

GV2ME16

9.00…14.0A

5.5

15

7.5

6

9

3

GV2ME20

13.0…18.0A

7.5

15

9

6

15

3

GV2ME21

17.0…23.0A

9

5

11

4

18.5

3

GV2ME22

20.0…25.0A

11

15

15

4

-

-

GV2ME32

24.0…32.0A

15

10

18.5

4

22

3

Additional functions of GV2ME Motor Circuit Breaker

■Unver voltage protection: Trip circuit breaker in case of under voltage, the user is therefore protected against sudden starting of the machine when normal voltage is restored;

■Remote off-power: Circuit breaker can be remotely tripped with the addition of a shunt trip;

■Off-power locking: The operators on both open-mounted and enclosed motor circuit breakers can be locked in the off position "O" by up to 3 padlocks;

Hot Tags: GV2ME Motor Circuit Breaker, China, Manufacturers, Suppliers, Factory